<% '============= Create and Open Database Connection ============= 'OPEN THE DATABASE If blnConnectToDB Then dim blnDBconnectionDown blnDBconnectionDown = false Err.Clear on error resume next set dbConn = Server.CreateObject("ADODB.Connection") 'Open the Connnection 'dbConn.Open Application("dbConn_ConnectionString") dbConn.Open "DSN=PostgreSQL30", "eere_news", "33reNews" ''New Error trapping. KC added 2/23/2012 If Err.Number <> 0 Then ''Response.Write (Err.Description& "

") dbConn.Close Set dbConn = nothing blnDBconnectionDown = true End If On Error GoTo 0 ''error trapping not working here KC removed 2/23/2012 ''tmpDBErrorNativeError = 0 '' For Each dbErr In dbConn.Errors '' strErrMsg = strErrMsg & _ '' "Source: " & dbErr.Source & vbCrLF & _ '' "Description: " & dbErr.Description & vbCrLF & _ '' "SQL State: " & dbErr.SQLState & vbCrLF & _ '' "NativeError: " & dbErr.NativeError & vbCrLF & _ '' "Number: " & dbErr.Number & vbCrLF & vbCrLF '' tmpDBErrorNativeError = dbErr.NativeError '' Next '' If (dbConn.Errors.Count > 0) AND (tmpDBErrorNativeError <> 5703) Then '' dbConn.Close '' Set dbConn = nothing '' blnDBconnectionDown = true '' Response.write(strErrMsg) '' Response.end '' End If dim arrErrors() Redim arrErrors(2,0) End If '============================================================== Public Function GetRS2(myCommand) On Error GoTo 0 'objConn: local connection object 'objRS: local recordset object 'objComm: command object passed in to the function Dim objConn, objRS, blnErrorLogged, objComm 'Create the command object Set objComm = Server.CreateObject("ADODB.Command") Set objComm = myCommand 'Create the connection object Set objConn = Server.CreateObject("ADODB.Connection") 'Open the connection object objConn.Open "DSN=PostgreSQL30", "eere_news", "33reNews" 'Set the active connection objComm.ActiveConnection = objConn 'Create the recordset object Set objRS = Server.CreateObject("ADODB.Recordset") 'Set the cursor location for disconnected recordsets 'objRS.CursorLocation = adUseClient 'Turn on error handling for just a second ' On Error Resume Next 'Open the recordset 'objRS.Open SQL, objConn, adOpenStatic, adLockOptimistic Set objRS = objComm.Execute 'Response.Write "State = " & objRS.State & "
" 'objRS.MoveLast 'objRS.MoveFirst 'Response.Write "Count = " & objRS.RecordCount & "
" 'Response.End 'Check for an error ' If Err.Number <> 0 Then ' Response.Write "Database Error Occured

" ' Response.Write "Error #" & Err.Number & "
" ' Response.Write Err.Description & "

" ' Response.Write "SQL:
" ' Response.Write SQL ' Response.End ' End If 'Turn off error handling ' On Error GoTo 0 'Disconnect the recordset 'Set objComm.ActiveConnection = Nothing 'Close the connection 'objConn.Close 'Set the connection to Nothing 'Set objConn = Nothing 'Set the Command to Nothing 'Set objComm = Nothing 'Return the recordset Set GetRS2 = objRS On Error Resume Next End Function '=============================================================== Function GetRS(sSQL) 'Declarations dim rs 'Create Recordset Object set rs = Server.CreateObject("ADODB.Recordset") If blnConnectToDB Then 'Open Recordset based on SQL rs.Open sSQL, dbConn, 1, 3, 1 End If 'Return Recordset set GetRs = rs End Function '=============================================================== Function ExecSQL(sSQL) 'Open the Command Object dim lRecordsAffected dbConn.Execute sSQL, lRecordsAffected 'Return the Records Affected ExecSQL = lRecordsAffected End Function '======================================================================== Function sendEmail(strFrom,strTo,strSubject,strMessage) Dim sch ' Schema sch = "http://schemas.microsoft.com/cdo/configuration/" Set cdoConfig = CreateObject("CDO.Configuration") With cdoConfig.Fields .Item(sch & "sendusing") = 2 .Item(sch & "smtpserver") = "mxrelay.doe.gov" .update End With Set cdoMessage = CreateObject("CDO.Message") With cdoMessage Set .Configuration = cdoConfig .From = strFrom .To = strTo .Subject = strSubject .TextBody = strMessage .Send End With Set cdoMessage = Nothing Set cdoConfig = Nothing End Function Function removeBadChars(tmpString) tmpString = Replace(tmpString , "<", "") tmpString = Replace(tmpString , ">", "") tmpString = Replace(tmpString , "'", "") tmpString = Replace(tmpString , """", "") tmpString = Replace(tmpString , ";", "") tmpString = Replace(tmpString , "(", "") tmpString = Replace(tmpString , ")", "") removeBadChars = tmpString End Function %> <% 'If there is a mobile version of this site, check the user_agent, and forward to 'the mobile version of the site (unless cookie or querystring var is set) if "true" = "true" then tmpSeeFullPage = Mid(Request.Querystring("m"),1,1) if ((isMobile) and (tmpSeeFullPage <> "1")) then tmpMobileURL = Request.servervariables("HTTP_URL") tmpMobileFileName = mid(tmpMobileURL, InStrRev(tmpMobileURL, "/")+1) tmpMobileURL = Left(tmpMobileURL, InStrRev(tmpMobileURL, "/")) tmpMobileURL = tmpMobileURL & "m/" & tmpMobileFileName Response.Clear Response.Redirect(tmpMobileURL) end if end if %>

<% ''This code is strictly when a user clicks on a left nav and needs to be forwarded to another site/program/office if ("" <> "") then Response.Clear Response.Redirect ("") end if %>

Covered Product Category: Residential Air-Source Heat Pumps

ENERGY STAR Qualified Products

FEMP provides acquisition guidance across a variety of product categories, including residential air-source heat pumps (ASHPs), which are an ENERGY STAR®-qualified product category. Federal laws and executive orders mandate that agencies meet these efficiency requirements in all procurement and acquisition actions that are not specifically exempted by law.

Most manufacturers display the ENERGY STAR label on complying models. For a model not displaying this label, check the manufacturer's literature to determine if it meets the efficiency requirements outlined by ENERGY STAR.

This product category overview covers the following:

Performance Requirements for Federal Purchases

For the most up-to-date efficiency levels required by ENERGY STAR, look for the ENERGY STAR label or visit the ENERGY STAR Product Specifications website. For more information, contact the FEMP point of contact listed at the bottom of this page.

Back to Top

Buying Energy-Efficient Air-Source Heat Pumps

ENERGY STAR's Product Specification applies to air-source heat pumps that operate on single-phase current and have capacities less than 65,000 British thermal units per hour (Btu/h). Units with such a capacity are typically used in residential applications. Window units and other ductless systems are excluded. Specify or select products that are ENERGY STAR-qualified. To find qualified products, go to the Consortium for Energy Efficiency (CEE) and Air Conditioning and Refrigeration Institute's (ARI) online directory at www.ceehvacdirectory.org. A guide that explains how to use this directory is available.

The Federal supply source for ASHPs is the General Services Administration (GSA), which sells them through its Multiple Awards Schedules program and online shopping network, GSA Advantage! When buying directly from commercial sources, look for the seasonal energy efficiency ratio (SEER) and heating season performance factor (HSPF) on the yellow EnergyGuide label required on these products. The energy efficiency ratio (EER), which is considered a better measure for determining peak load, can be found in the manufacturer's product information or website.

These requirements apply to all forms of procurement, including guide and project specifications; construction, renovation, repair, energy service, operation and maintenance (O&M) contracts; lease agreements; and solicitations for offers. Energy performance requirements should be included in all evaluations of solicitation responses. Buyers shall insert the standard clause from FAR section 52.223-15 into contracts and solicitations that deliver, acquire, furnish, or specify energy-consuming products for use in Federal facilities. Agencies can claim an exception to these requirements through a written finding that no ENERGY STAR-qualified or FEMP-designated product is life-cycle cost effective for a specific application.

Back to Top

Buyer Tips

Federal buyers should require that ASHPs be installed in accordance with the HVAC Quality Installation (QI) Specification published by the Air Conditioning Contractors of America. Installation problems like oversizing, poorly designed distribution systems, and leaky ducts result in efficiency losses, occupant discomfort, and shortened equipment life. Requiring the contractor to follow the HVAC QI Specification will ensure that these and other problems are addressed and the energy and cost savings achieved.

Back to Top

User Tips

ASHPs are frequently selected based on their cooling capacity. To make up for deficiencies with the heating capacity, electric resistance elements are typically added. Because of the inefficient nature of these heating elements, their use should be kept to a minimum. Consider using a programmable thermostat to minimize unnecessary operation of the unit. Thermostats specifically designed for heat pumps, which ramp the temperature up slowly to avoid activating the electric resistance heating elements, should be installed.

Regular maintenance (e.g., charging refrigerant, replacing filters, etc.) is necessary to maintain peak performance.

Back to Top

Estimating Energy and Cost Savings

ENERGY STAR has an Excel-based cost calculator for ASHPs. To modify the utility price, go to and click on "Savings Calculator" in the column on the right. Input the HSPF, SEER, capacity of the ASHP, and the rate for electricity at your facility. The output section will automatically display results that more accurately reflect your energy use and cost.

Back to Top

For More Information

Federal supply sources are the U.S. General Services Administration (GSA) and Defense Logistics Agency (DLA). GSA sells products through its Multiple Awards Schedules and GSA Advantage! DLA offers products through the Defense Supply Center Philadelphia and DOD EMALL.

The following resources are available for additional information:

Amanda Sahl
Federal Energy Management Program
202-586-1662
amanda.sahl@ee.doe.gov

Lawrence Berkeley National Laboratory provided supporting analysis for this acquisition guidance.